INSTALLING

Continued

INSTALLATION AND CLEARANCES (Vent-Free Operation Only)

WARNING

Maintain the minimum clearances. If you can, provide greater clear- ances from floor, ceiling, and adjoining wall.

 

MINIMUM FIREPLACE CLEARANCE

 

TO COMBUSTIBLE MATERIALS

Log Size

 

Side Wall

Ceiling

 

 

 

 

24"

 

16"

42"

 

 

 

 

LOG SIZING REQUIREMENTS

Log

Minimum Firebox Size

 

 

Size

Height

 

Depth

Front Width

24"

17"

 

14"

26"

 

 

 

 

 

Carefully follow the instructions below. This will ensure safe installation into a masonry or U.L. listed manufactured fireplace.

Minimum Wall and Ceiling Clearances (see Figure 4)

A.Clearances from the side of the fireplace opening to any combustible wall should not be less than 16 inches.

B.Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.

42"

16"

Left and Right

Sides

Figure 4 - Minimum Clearance to Wall and Ceiling