OWNER’S MANUAL

AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: Space size 18 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2304 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 2304 cu. ft. (volume of space) ÷ 50 cu. ft. = 46.1 or 46,100 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

___________________ Btu/Hr

 

 

 

 

Gas water heater*

___________________ Btu/Hr

Example:

 

 

 

Gas furnace

___________________ Btu/Hr

Gas water heater

 

40,000

Btu/Hr

Vented gas heater

___________________ Btu/Hr

Vent-free heater

+

10,000

Btu/Hr

50,000

Gas fireplace logs

___________________ Btu/Hr

Total

=

Btu/Hr

Other gas appliances* + ___________________ Btu/Hr

 

 

 

 

Total

= ___________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 46,100 Btu/Hr (maximum the space can support) 50,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Continued

105563

5

Page 5
Image 5
Desa FB-2B installation manual AIR for Combustion Ventilation, Determining FRESH-AIR Flow for Heater Location

FB-2B specifications

The Desa FB-2B is an innovative and versatile piece of technology designed to cater to a wide range of applications, particularly in industries where performance, reliability, and efficiency are paramount. This ground-breaking product incorporates cutting-edge features and technologies that set it apart from its competitors.

One of the standout features of the Desa FB-2B is its robust construction, which ensures durability and longevity, even in demanding environments. This unit is built to withstand harsh conditions, making it an ideal choice for heavy-duty applications. The materials used in its manufacturing process have been carefully selected to guarantee resistance to wear and tear, as well as potential chemical exposure.

In terms of technology, the Desa FB-2B is equipped with advanced automation capabilities. This feature allows for seamless integration into existing systems, enabling users to operate it with minimal manual intervention. The automation technology enhances overall efficiency, as it reduces human error and optimizes performance.

Another significant aspect of the Desa FB-2B is its energy efficiency. The device has been engineered to consume minimal power while delivering maximum output. Its intelligent energy management system monitors usage and adjusts performance accordingly, ensuring that energy is used effectively without compromising on productivity.

The Desa FB-2B also boasts an intuitive user interface, making it accessible for operators of all skill levels. The user-friendly design facilitates quick adjustments and monitoring, enhancing overall operational effectiveness. Additionally, the interface is equipped with real-time data analytics, providing users with insights into performance metrics that could help drive further improvements.

Safety features are paramount in the design of the Desa FB-2B. It includes multiple fail-safes and alert systems to ensure that operators are informed of any potential issues before they escalate. This emphasis on safety contributes to a more secure working environment, making it suitable for applications where human interaction is a factor.

In summary, the Desa FB-2B is a remarkable piece of equipment that combines durability, advanced technology, energy efficiency, and user-friendly design. Its features make it an exceptional choice for industries that demand high-performance solutions, ensuring that users can rely on it for their operational needs. With its focus on safety and automation, the Desa FB-2B is truly a leader in its field.