MINIMUM CLEARANCE

LFP33NR

UNVENTED NATURAL GAS FIREPLACE

INSTALLATION

Continued

INSTALLATION

CLEARANCES

WARNING: Maintain the mini- mum clearances. If you can, pro- vide greater clearances from floor, ceiling, and adjoining wall.

Carefully follow the instructions below. This will ensure safe installation.

Minimum Wall and Ceiling Clearances (see Figure 7)

A. Clearances from the side of the fire- place opening to any combustible wall should not be less than 16 inches for a cabinet mantel or 12 inches for a cor- ner installation.

B. Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.

Note: Clearances

 

Side Wall - 16"

 

Cabinet and

are the same if

 

42"

Face Mantel

using optional

cabinet mantel or

 

Ceiling - 42"

 

Corner Mantel

built-in installation.

 

 

Floor - 0"

 

 

16"

Figure 7 - Minimum Clearance to Wall and Ceiling

CONVENTIONAL FIREPLACE INSTALLATION

Conventional installation of this fireplace involves installing fireplace along with the corner, face, or cabinet mantel with hearth base accessories against a wall in your home. Follow the instructions below to install the fireplace in this manner.

Note: The instructions below show installa- tion using the cabinet mantel and hearth base accessories (see Accessories, pages 24 and 25). The hearth base accessory shown is optional for this installation. You can install fireplace and cabinet mantel directly on the floor. The corner mantel accessory cannot be installed with the hearth bases. You must install corner mantel directly on the floor.

1.Assemble cabinet mantel, hearth base, and trim accessories. Assembly instruc- tions are included with each accessory.

2.When installing blower, install a prop- erly grounded, 120 volt three-prong electrical outlet at fireplace location if an outlet is not there. If possible, lo- cate outlet so cabinet mantel will cover it when installed (see Figure 8).

3.Install gas piping to fireplace location. This installation includes an approved flexible gas line (if allowed by local codes) after the manual shutoff valve. The flexible gas line must be the last item installed on the gas piping. See In- stalling Gas Piping to Fireplace Loca- tion, page 10.

4.Place hearth base accessory against wall at installation location. Cut an ac- cess hole in hearth top to run flexible gas line to fireplace (see Figure 8). Make sure to locate access hole so cabi- net mantel will cover it when installed. Note: You can secure base to floor us- ing wood screws. Countersink screw heads and putty over.

5.Route flexible gas line through access hole in hearth base.

6.Center cabinet mantel on hearth base (see Figure 9). Make sure mantel is flush against wall.

7.Break off nailing flanges (see Figure 10, page 9) with hammer or pliers.

8.Place cardboard or other protective material on top of hearth base. Care- fully set fireplace on protective mate- rial, with back of fireplace inside man- tel opening.

9.Attach flexible gas line to fireplace gas regulator. See Connecting Fireplace to Gas Supply, page 11.

10.If blower is installed, route blower elec- trical cord through access holes in ei- ther side of fireplace. Note: Bushing may be moved if necessary. Plug elec- trical cord into electrical outlet.

 

Flexible

Electrical

Gas Line

Hearth

Outlet

Access

Gas Line

Base

 

Hole

 

 

Figure 8 - Placing Hearth Base Accessory Against Wall

Cabinet

Mantel

Figure 9 - Installing Cabinet Mantel

8

104887

Page 8
Image 8