Desa RCLP155AT Troubleshooting, Technical Service, Accessory, Observed Fault, Possible Cause

Models: RCLP155AT

1 24
Download 24 pages 63.56 Kb
Page 8
Image 8
TROUBLESHOOTING

TROUBLESHOOTING

OBSERVED FAULT WARNING: Never service heater while it is plugged in, connected to propane supply, operating or hot. Severe burns and electrical shock can occur.

OBSERVED FAULT

POSSIBLE CAUSE

REMEDY

 

 

 

 

 

Fan does not turn when heater is

1.

No electrical power to heater

1.

Check voltage to electrical

plugged in

 

 

 

outlet. If voltage is good, check

 

 

 

 

heater power cord for breaks

 

2.

Fan hitting inside of heater

2.

Adjust motor/fan mount to

 

 

shell

 

keep fan from hitting inside of

 

 

 

 

heater shell. Bend fan mount

 

 

 

 

if necessary

 

3.

Fan blades bent

3.

Replace fan. See Fan, page 6

 

4.

Defective motor

4.

Replace motor

 

 

 

 

 

Heater will not ignite

1.

User did not follow installa-

1.

Repeat installation and operation

 

 

tion or operation instructions

 

instructions. See Installation,

 

 

properly

 

page 4 and Operation, page 5

 

2.

No spark at ignitor. See Ig-

2.

A) Check ignitor wire. Tighten

 

 

nitor, page 7. If you see spark

 

or reattach loose ignitor wire.

 

 

at ignitor, have heater serviced

 

B) Assure gap between ignitor

 

 

by qualified service person. If

 

electrode and target plate is

 

 

no spark seen:

 

0.13"0/.15" (3.3/3.8 mm). Do

 

 

A) Loose or disconnected

 

not bend electrode. Doing so

 

 

ignitor wire

 

may cause it to break

 

 

B) Wrong spark gap

 

C) Replace ignitor electrode

 

 

C) Bad ignitor electrode

 

 

Heater shuts down while run- ning

POSSIBLE CAUSE WARNING: Use only in areas free of high dust content.

1.Propane supply may be inad- equate

2.High surrounding air tem- perature causing thermal limit device to shut down heater.

3.Restricted air flow

4.Damaged fan

5.Excessive dust or debris in surrounding area

1.A) Refill tank

B)Provide additional and/or larger tanks. See Propane Supply, page 3

2.This can happen when running heater in temperatures above 85° F (29˚ C). Run heater in cooler temperatures

3.Check heater inlet and outlet. Remove any obstructions

4.Replace fan. See Fan, page 6

5.Clean heater. See Mainte- nance, page 6

TECHNICAL SERVICE

You may have further questions about this heater. If so, contact DESA Heating Productsʼ Technical Service Department at 1-866-672-6040. When calling, please have your model and serial numbers of your heater ready.

You can also visit DESA Heating ProductsʼTechni- cal Service web site at www.desatech.com.