INSTALLATION
WARNING: Review and un- derstand the warnings in the Safety Information section, page
2.They are needed to safely op- erate this heater. Follow all local codes when using this heater.
WARNING:Testallgaspiping and connections for leaks after installing or servicing. Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.
1.Provide propane/LP supply system (see Pro- pane/LP Supply, page 4).
2.Connect POL fitting on hose/regulator assem- bly to propane/LP tank(s). Turn POL fitting counterclockwise into threads on tank. Tighten firmly using a wrench. IMPORTANT: Tighten regulator with black adjustment knob point- ing down. Pointing adjustment knob down protects regulator from weather damage.
3.Connect hose to inlet connector. Tighten firmly using a wrench.
IMPORTANT: Extra hose or piping may be used if needed. Install extra hose or pip- ing between hose/regulator assembly and propane/LP tank. You must use the regulator supplied with the heater.
4.Open propane/LP supply valve on propane/LP tank(s) slowly. Note: If not opened slowly, ex-
Supply | POL Fitting | |
Hose | ||
Valve | ||
|
Propane/LP | Regulator |
Tank |
|
| Adjustment Knob |
| (pointing down) |
Figure 3 - Regulator With Adjustment
Knob Pointing Down
5.Adjust regulator between 7 and 20 psig. Note: Higher regulator setting will allow heater to produce more heat.
6.Check all connections for leaks.
7.Close propane/LP supply valve.
WARNING: Do not adjust regulator below 7 psig or above 20 psig. Heater may not run properly.
Hose
Inlet Connector
Figure 4 - Hose and Inlet Connector
OPERATION
WARNING: Review and un- derstand the warnings in the Safety Information section, page
2.They are needed to safely op- erate this heater. Follow all local codes when using this heater.
TO START HEATER
1.Follow all installation, ventilation and safety information.
2.Locate heater on stable and level surface. Make sure strong drafts do not blow into front or rear of heater.
3.Plug power cord of heater into a
Extension Cord Size Requirement
Up to 50 feet (15 m) long, use 18 AWG rated cord.
51 to 100 feet (15.5 to 30.5 m) long, use 16 AWG rated cord.
101 to 200 feet (30.78 to 61 m) long, use 14 AWG rated cord.
4.Plug extension cord into a 120 volt/60 hertz,
www.desatech.com | 5 |