Desa SMS18 WARNINGAqualified service, personmustconnectlogsettogas, supply. Follow all local codes

Models: SMS24 SMS18

1 16
Download 16 pages 20.36 Kb
Page 6
Image 6
INSTALLING DAMPER CLAMP

INSTALLATION

Continued

INSTALLING DAMPER CLAMP

Secure the damper stop clamp provided to the leading edge of the damper as shown in Figure 3. If for any rea- son this clamp doesn't work on your fireplace, another suitable clamp or permanent stop must be installed, or the damper blade must be cut or removed.

Damper

Clamp

Damper

 

Damper

Damper

Clamp

 

Masonry Fireplace

Manufactured

 

Fireplace

Figure 3 - Attaching Damper Clamp

CONNECTING TO GAS SUPPLY

WARNING:Aqualified service

personmustconnectlogsettogas

supply. Follow all local codes.

Installation Items Needed

Before installing log set, make sure you have the

items listed below.

 

piping (check local codes)

sealant (resistant to Propane/LP gas)

equipment shutoff valve

test gauge connection

adjustable (crescent) wrench or pliers

sediment trap

tee joint

pipe wrench

Masonry FireplaceCAUTION:Useonlynew,black ironorsteelpipe.Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas vol- ume to log set. If pipe is too small, undue loss of volume will occur.

Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from log set (see Figure 4).

IMPORTANT: Install equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in a clogged burner injector.

Fireplace WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install a sediment trap in supply line as shown in Figure 4. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and appliance. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into log set controls. If sediment trap is not installed or is installed wrong, log set may not run properly.

Approved Flexible Gas Hose (if allowed by local codes)

CSA Design-Certified Equipment Shutoff Valve With 1/8" NPT Tap*

 

From Gas Meter

 

(5" W.C.** to

 

10.5" W.C.

 

Pressure)

3" Minimum

 

 

Cap

Pipe

Tee

Nipple Joint

 

Sediment Trap

Figure 4 - Gas Connection

*Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 13.

** Minimum inlet pressure for purpose of input adjustment.

6

www.desatech.com

117536-01B

Page 6
Image 6
Desa SMS18 WARNINGAqualified service, personmustconnectlogsettogas, supply. Follow all local codes, Continued, Fireplace