INSTALLING

* An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an acceptable

alternative to test gauge connection. Purchase the optional A.G.A. design-certified manual

 

Continued shutoff valve from your dealer. See Accessory, page 30.

 

The gas regulator for the stove heater is located on the lower right-hand side of the

 

stove when viewed from the front of the unit. The gas connection can be made either

 

through the bottom right side or through the lower back opening as illustrated in

 

Figure 17. Make sure gas log heater is secured to the stove cavity assembly.

 

Side View

Back View

Front of

Back Stove Panel

Stove Unit

 

Product

Gas

Identification

Label

Regulator

 

Access

 

Gas Log

Heater

Figure 17 - Gas Regulator Location and Gas Line Access Into Stove Cabinet

WARNING

WARNING ICON

G 001

Never connect heater to private (non-utility) gas wells. This gas is commonly known as wellhead gas.

CAUTION

WARNING ICON

G 001

Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of pressure will occur.

Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be up- stream from heater (see Figure 18, page 16).

Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

CAUTION

WARNING ICON

G 001

Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

Install sediment trap in supply line as shown in Figure 18, page 16. Locate sedi- ment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contami- nants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

Continued

15

 

104024

Page 15