Desa SVYD18NRA/PRA SERIES Checking GAS Connections, Pressure Testing Gas Supply Piping System

Models: SVYD18NRA/PRA SERIES

1 28
Download 28 pages 36.32 Kb
Page 13
Image 13

INSTALLATION

Continued

CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fittings.

 

PROPANE/LP

 

From External

CSA Design-Certified

Regulator

(11" W.C. to 14"

Equipment Shutoff Valve

With 1/8" NPT Tap*

W.C. Pressure)

NATURAL

Approved

From Gas

Flexible Gas

Meter (5" W.C.

Hose (if

to 10.5" W.C.

allowed by

Pressure)

local codes)

 

3" Min

 

Cap Pipe Tee

Gas Control

Nipple Joint

 

Sediment Trap

Figure 16 - Gas Connection

(SVYD18PRA/NRA Series)

*Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 27.

**Minimum inlet pressure for purpose of input adjustment.

CHECKING GAS CONNECTIONS

WARNING: Test all gas pip- ing and connections, internal and external to unit, for leaks after installing or servicing. Cor- rect all leaks at once.

CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and heater.SeeguidelinesunderCon- necting to Gas Supply, page 11.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equip- ment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve lo- cated on or near gas meter for natural gas, or using compressed air.

4.Check all joints of gas supply piping system. Apply a noncorrosive leak detection fluid to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 17).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve lo- cated on or near gas meter for natural gas, or using compressed air.

3.Check all joints from gas meter for natural or propane/LP supply to equipment shutoff valve (see Figure 18 or 19, page 14). Apply a non- corrosive leak detection fluid to gas joints. Bubbles forming show a leak.

WARNING: Never use an

4. Correct all leaks at once.

open flame to check for a leak. Apply a noncorrosive leak de- tection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Equipment Shutoff Valve

OpenN

POSIT

Closed

Figure 17 - Equipment Shutoff Valve

113084-01A

www.desatech.com

13

Page 13
Image 13
Desa SVYD18NRA/PRA SERIES installation manual Checking GAS Connections, Pressure Testing Gas Supply Piping System