SPECIFICATIONS

6

SPECIFICATIONS TROUBLESHOOTING ACCESSORIES

SPECIFICATIONS

Rating (BTU/Hr)

High - 200,000

 

Low - 100,000

Fuel

Propane Vapor Only

Fuel Consumption

Gallons/Hour - 1.09min./2.19 max.

 

Pounds/Hour - 4.64min./9.28 max.

Supply Pressure (To Regulator)

Maximum - 200 psi Minimum - 20 psi (for input adjustment)

Manifold Pressure

High - 4.6 psi

 

Low - 5.9 psi

Weight (lbs)

16

Shipping Weight (lbs)

20

Size - L x W x H (in.)

30 x 15 x 16

Minimum Temp.

-20°F (-29°C) Surrounding Air

TROUBLESHOOTING

You may have further questions about this heater. If so, contact DESA International’s Technical Service Department at 1-866-672-6040.

ACCESSORIES

Purchase these accessories and parts from your local dealer or service center. If your dealer or service center can not supply an accessory or part, contact your nearest Parts Central (listed in the separate Authorized Service Center booklet) or call DESA Interna- tional at 1-866-672-6040 for referral information. You can also write to the address listed on the back page of this manual.

Part Number

Description

LPA1020

10' Rubber Hose with Brass Fitting

 

U.L. listed.

LPA2005

Propane Gas Regulator

 

U.L. listed.

LPA3005

Hose/Regulator Assembly

 

U.L. listed.

LPA4020

Fuel Gas Connector

 

Connects regulator to all standard

 

propane tanks. U.L. and A.G.A. listed.

TROUBLESHOOTING WARNING: Never attempt to service heater while it is connected to propane supply, operating, or hot. Severe burns can occur.

SYMPTOM

POSSIBLE CAUSE

REMEDY

Burner fails to light

1.

Propane supply valve closed on propane

1.

Open propane supply valve slowly

 

 

tank(s)

 

 

 

2.

Excess-flow check valve closed

2.

Close propane supply valve on propane

 

 

 

 

tank and reopen slowly

 

3.

Blockage in burner nozzle

3.

Replace burner nozzle

 

4.

Piezo ignition system not sparking

4.

Check to assure ignitor electrode gap is

 

 

 

 

.130". Check wire lead for damage. Re-

 

 

 

 

place piezo ignitor and/or ignitor elec-

 

 

 

 

trode as necessary

 

 

 

 

 

Burner lights but goes out when automatic

1.

Not enough warm-up time

1.

Relight, hold automatic control valve

control valve button is released

 

 

 

button in 45 seconds

 

2.

Low gas pressure

2.

Check propane tank(s) for proper gas

 

 

 

 

supply

 

3.

Thermocouple loose or needs to be re-

3.

Tighten connection or replace thermo-

 

 

placed

 

couple

 

4.

Automatic control valve needs to be re-

4.

Replace automatic control valve

 

 

placed

 

 

 

 

 

 

 

Burn rate is low

1.

Main burner valve not fully open

1.

Fully open main burner valve by turn-

 

 

 

 

ing control knob towards HIGH posi-

 

 

 

 

tion until it stops

 

2.

Plugged gas orifices

2.

Replace gas orifice

 

3.

Low gas pressure

3.

Check gas supply; check regulator output

 

4.

Low fuel supply

4.

Consult propane gas supplier

For more

 

visit www.

 

.com

103886-01F