| INSTALLATION |
| Continued |
|
|
Noncombustible |
|
Material | Requirements for |
Distance (A) | Safe Installation |
|
|
12" or more | Noncombustible material OK. |
Between 8" | 24" Model:Install fire place hood accessory |
and 12" | (GA6060, see Accessories, page 25). |
| 18" Model: Noncombustible material OK |
Less than 8" | Noncombustible material must be |
| extended to at least 8". See Between 8" |
| and 12", above. If you cannot extend material, |
| you must operate heater with flue damper |
| open. |
|
|
Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace
10"
8"
6"
2 1/2"
Minimum Non- |
|
| (A) | |
| ||||
Combustible | ||||
| ||||
Material |
| |||
|
|
| 12" | |
|
|
|
|
Mantel Shelf
18" |
| 20" | 22" |
| |||
|
|
|
|
Underside of
Mantel Shelf
All minimum distances are in inches
24"
Top of Fireplace
Opening
Minimum Non- | Distances to |
Combustible | Underside of |
Material Height | Mantel |
Figure 6 - Minimum Mantel Clearances Without Using Hood
12"
10"
8"
6"
2 1/2"
Minimum
Noncombustible
Material8"
Min.
Mantel Shelf
Underside
of Mantel
Shelf
All minimum distances are in inches
12" | 15" | 18" | 20" |
Hood (GA6050, GA6052 or GA6053)
Distances to Underside of Mantel
Top of
Fireplace
Opening
Figure 7 - Minimum Mantel Clearances When Using Hood
10 | www.desatech.com |