Desa VF-18P-PJD, VF-24N-PJD Installation, Checking Gas Connections, Natural Gas, Propane/LP Gas

Models: VF-24N-PJD

1 32
Download 32 pages 60.09 Kb
Page 13
Image 13
Natural Gas

INSTALLATION

Continued

Installation must include an equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 12).

IMPORTANT: Install equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special re- quirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

Propane/LP Gas WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

To Gas

CSA Design-Certified

Equipment Shutoff Valve

Control

With 1/8" NPT Tap*

 

 

Natural Gas

 

From Gas Meter

Approved

(5" W.C.** to 10.5"

W.C. Pressure)

Flexible Gas

Propane/LP Gas

Hose (if allowed

From External

by local codes)

Regulator

 

 

(11" W.C.** to

3" Minimum

14" W.C.

Pressure)

 

Cap Pipe Tee

Nipple Joint

Sediment Trap

Figure 12 - Gas Connection

*Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 25.

** Minimum inlet pressure for purpose of input

adjustment.

We recommend that you install a sediment trap in supply line as shown in Figure 12. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or

is installed wrong, heater may not run properly.

CHECKING GAS CONNECTIONS CAUTION: Avoid damage to gas control. Hold gas control with wrench when connecting it to gas piping and/or fittings.

CHECKING GAS CONNECTIONS

PRESSURE TESTING GAS SUPPLY PIPING SYSTEMWARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa) WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Manual background CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and heater. See guidelines un- der Connecting to Gas Supply, page 12.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

111826-04A

www.desatech.com

13

Page 13
Image 13
Desa VF-18P-PJD, VF-24N-PJD installation manual Installation, Checking Gas Connections, Natural Gas, Propane/LP Gas