Desa VML27PR installation manual Mantel Clearances, Minimum Noncombustible Material Clearances

Models: VML27PR

1 28
Download 28 pages 14.4 Kb
Page 8
Image 8

8

INSTALLATION

Installation and Clearances (Cont.) Mantel Clearances

INSTALLATION

Continued

Minimum Noncombustible Material Clearances

If Not Using Mantel

Note: If using a mantel, proceed to If Using Mantel. If not using a mantel, follow the information below.

You must have noncombustible material(s) above both fireplace openings. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8" up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory. See Figure 5 at right for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Install- ing Damper Clamp Accessory for Vented Operation, page 9.

If Using Mantel

You must have noncombustible material(s) above the fireplace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8 inches up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory. Even if noncombustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 5 and 6 and Figure 7, page 9, for minimum clearances.

Noncombustible

Requirements for

Material Distance (A)

Safe Installation

 

 

12" or more

Noncombustible material OK.

Between 8" and 12"

Install fireplace hood accessory

MANTEL CLEARANCES

In addition to meeting noncombustible material clearances, you must also meet required clearances between fireplace openings and mantel shelf on each side of the fireplace. If you do not meet the clearances listed below, you will need a hood.

Determining Minimum Mantel Clearance

If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).

Determining Minimum Mantel Clearance When using a Hood

If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clearances shown in Figure 7, page 9 when using hood.

NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.

NOTICE: If your installation does not meet the mini- mum clearances shown, you must do one of the following:

operate the logs only with the flue damper open

raise the mantel to an acceptable height

remove the mantel

 

(GA6050, GA6052 or GA6053, see

 

Accessories, page 27).

Less than 8"

Noncombustible material must be

 

extended to at least 8". See Between

 

8" and 12", above. If you cannot

 

extend material, you must operate

 

heater with flue damper open.

Heat Resistant

Material

(A)

10"

8"

6"

2 1/2"

Minimum Non-

 

 

(A)

 

Combustible

 

Material

 

 

 

 

12"

 

 

 

 

Mantel Shelf

18"

 

20"

22"

 

 

 

 

 

Underside of

Mantel Shelf

All minimum distances are in inches

24"

Top of Fireplace

Opening

Minimum Non-

Distances to

Combustible

Underside of

Material Height

Mantel

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.)

Figure 6 - Minimum Mantel Clearances Without Using Hood

Above Fireplace

 

For morevisit www..com

111115-01D

Page 8
Image 8
Desa VML27PR Mantel Clearances, Minimum Noncombustible Material Clearances, Determining Minimum Mantel Clearance