Desa VN1000B Connecting To Gas Supply, Continued, Pressure Testing Heater Gas Connections

Models: VN1000B

1 28
Download 28 pages 51.73 Kb
Page 15
Image 15
PRESSURE TESTING HEATER GAS CONNECTIONS

CONNECTING TO GAS SUPPLY

Continued

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Figure 13).

2.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to manual shutoff valve (see Figure 14). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

PRESSURE TESTING HEATER GAS CONNECTIONS

1.Open manual shutoff valve (see Figure 13).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual shutoff valve to control valve (see Figure 14). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 16 through 18). Check the rest of the internal joints for leaks.

7.Turn off heater (see To Turn Off Gas To Appliance, page 18).

8.Replace front panel.

Open

Manual

Shutoff

Valve

Closed

Figure 13 - Manual Shutoff Valve

Control Valve Location

Gas Meter

Manual

Shutoff

Valve

Figure 14 - Checking Gas Joints

15

099400

Page 15
Image 15
Desa VN1000B installation manual Connecting To Gas Supply, Continued, Pressure Testing Heater Gas Connections