AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow For Heater Location

5

AIR FOR COMBUSTION AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

 

 

Gas water heater

 

40,000

 

_____________ Btu/Hr

Vent-free heater

+

20,000

_____________ Btu/Hr

Total

=

60,000

_____________ Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

60,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the ex- tra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Out- doors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room un- confined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

For morevisit www..com

107887-01E

Page 5
Image 5
Desa VP16IT, VN18 Determining FRESH-AIR Flow for Heater Location, Determining if You Have a Confined or Unconfined Space

VN18, VP16, VN18T, VN25IT, VP22IT specifications

Desa VN18, VN30T, VP16, VP26T, and VP16T are a series of innovative devices tailored to meet diverse needs in various applications, ranging from industrial to consumer markets. Each model embodies distinct features, technologies, and characteristics that enhance performance and usability.

The Desa VN18 is renowned for its compact structure and lightweight design, making it ideal for small-scale applications. It integrates a sophisticated energy-efficient system that minimizes power consumption while maximizing output. This model supports various connectivity options, ensuring seamless integration with existing systems. Additionally, the VN18 is equipped with an intuitive user interface that simplifies operation, making it accessible even for those with limited technical experience.

In contrast, the VN30T offers enhanced capabilities suitable for medium to large-scale operations. This model boasts an impressive processing power, enabling it to handle more complex tasks with ease. The VN30T features advanced cooling technologies that keep the unit operating optimally, even under heavy workloads. Furthermore, its durable construction ensures longevity and reliability, making it a preferred choice for industrial environments.

The VP16, designed with versatility in mind, excels in adaptability across multiple applications. It offers interchangeable components, allowing users to customize setup based on specific needs. The technology embedded within the VP16 includes smart sensors that provide real-time feedback, helping users to monitor performance and adjust settings accordingly. This level of adaptability makes the VP16 an invaluable asset in dynamic working conditions.

Next in the lineup is the VP26T, which stands out for its robust performance under demanding conditions. With a focus on safety features, this model includes multiple fail-safes and redundancy systems that ensure consistent operation, even in emergencies. The VP26T is designed for heavy-duty applications, featuring enhanced materials that resist wear and tear, thereby prolonging its lifespan.

Finally, the VP16T combines the best aspects of its predecessors while introducing new technological advancements. It utilizes cutting-edge automation technologies that enable remote control and monitoring, enhancing user convenience. The VP16T's power management system optimizes energy use based on operational demands, contributing to both cost savings and sustainability.

Overall, Desa VN18, VN30T, VP16, VP26T, and VP16T represent a forward-thinking approach to design and functionality, addressing the evolving needs of users across various sectors. With their unique features and robust technologies, these models are set to redefine standards in their respective categories.