Desa VP30BT, VP20BT, VN30BT, VN20BT installation manual Installation, WARNING Use pipe joint

Models: VN20BT VN30BT VP30BT VP20BT

1 24
Download 24 pages 12.88 Kb
Page 12
Image 12
 WARNING: Use pipe joint

INSTALLATION

Continued

Manual backgroundCAUTION:Useonlynew,black ironorsteelpipe.Internally-tinned

IMPORTANT: Hold the pressure regulator with wrench when connecting it to gas piping and/or fittings. Do not over tighten pipe connection to regulator. The regulator body could be damaged.

copper tubing may be used in cer- tainareas.Checkyourlocalcodes. Usepipeoflargeenoughdiameter to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.

Typical Inlet Pipe Diameters VN20BT, VP20BT - 3/8" or greater

VN30BT, VP30BT - 1/2" or greater

Installation must include equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 15).

IMPORTANT: Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

Manual background WARNING: Use pipe joint

 

Pressure

 

Regulator

3/8" NPT

Pipe Nipple

Connection*

Tee Joint

 

 

Reducer

 

Bushing

Gauge

to 1/8"

NPT

 

 

1/8" NPT

Test

Plug Tap

 

Trap

Tee Joint

Pipe

Sediment

Nipple

 

 

Cap

Note: Burner bracket not shown for clarity

Heater Cabinet

Ground Joint

Union

Manual background Equipment

Shutoff

Valve *

3" Min.

Natural Gas From Gas Meter (4" W.C. to 10.5" W.C. Pressure) Propane/LP From External Regulator (11" W.C. to 14" W.C. Pressure)

sealant that is resistant to liquid petroleum (LP) gas.

Install sediment trap in supply line as shown in Figure 15. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

 

External

Propane/LP

Regulator

Supply Tank

 

Vent

Pointing

Down

Figure 14 - External Regulator With Vent

Pointing Down

Figure 15 - Gas Connection

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 21.

CHECKING GAS CONNECTIONS

Manual background WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.

Manual background WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.