Figure 2 - Technical Information Charts

Installation

Continued

 

 

 

 

 

Burner

 

Btu

 

MinIMUM Vent

 

 

Model

 

 

DESCRIPTION

 

Input

 

Opening

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VTD-18N-JHB

 

18" Ramp

 

59,000

 

8" dia.

 

 

 

VTD-24N-JHB

 

24" Ramp

 

69,000

 

8" dia.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VTD-30N-JHB

 

30" Ramp

 

74,000

 

8" dia.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MINIMUM FIREBOX SIZES

 

 

 

 

 

 

MODEL

 

FRONT WIDTH

BACK WIDTH*

 

DEPTH

 

HEIGHT

 

 

 

 

 

 

 

 

 

 

VTD-18N-JHB

 

 

28"

 

16"

 

14"

 

18"

VTD-24N-JHB

 

 

29 3/4"

 

17"

 

15 1/2"

 

18"

VTD-30N-JHB

 

 

36"

 

27"

 

18"

 

18"

*At depth indicated

BURNER ORIFICE

 

NATURAL

LOG SIZE

INCHES

NUMBER

18"

0.1495

25

24"

0.1570

22

30"

0.1660

19

FUEL INLET PRESSURE SPECIFICATIONS (W.C.)

 

MIN.

MAX.

 

 

 

NG

5.5"

10.5"

Figure 2 - Technical Information Charts

VENTING SPECIFICATIONS FOR INSTALLATION

The fireplace chimney flue and vent must be draft- ing properly. To check the vent for proper drafting: Light a tightly rolled newspaper on one end and place it at the inside front edge of the fireplace. Observe the smoke and be sure the vent is properly drawing it up the chimney. If the smoke spills out into the room, extinguish the flame and remove any obstruction until proper venting is achieved.

The chimney flue must remain open a minimum of 3" at all times during the operation of this log set.

Installing Damper Clamp

Secure the damper stop clamp to the edge of the damper as shown in Figure 3. If for any reason this clamp doesn't work on your fireplace, another suit- able clamp or permanent stop must be installed, or the damper blade must be cut or removed.

Damper

Clamp

Damper

Damper

VENTING SPECIFICATIONS FOR INSTALLATION Clamp

DamperDamper

Masonry Manufactured

FireplaceFireplace

Figure 3 - Attaching Damper Clamp