Venting Installation

instructions

Continued

Horizontal Termination Configurations

Figures 14 through 18 show different configurations and alterna- tives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: If using a venting configuration of only horizontal venting with no vertical run, a 1/4" rise for every 12" of run toward the termination is required.

WARNING: Never run vent downward as this may cause excessive temperatures which could cause a fire. Operation of improperly installed and maintained venting system could result in serious injury, property damage or loss of life.

GROUND FLOOR INSTALLATION

Recommended Applications:

Installation using cabinet surrounds

Through the wall using round or square termination (up to 12" horizontal pipe)

NOT FOR CORNER INSTALLATION

Adjustable

45° Elbow

Pipe 12" Max.

 

CORNER AND ALTERNATE INSTALLATION

Recommended Applications:

Corner ground floor installation

Ground floor installation where pipe vents horizontally through wall (over 12" horizontal pipe)

Basement installation where one foot clearance from ground to termination is possible

 

Not to Exceed

90° Elbow

 

(H) Limits

Wall

 

 

 

Firestop

 

As Required for (V)

 

 

 

 

See Chart for Pipe

 

 

Section Required

Square

 

 

Termination

45°

 

 

 

 

Elbow

 

Required

Vertical (V) Vertical Pipe Horizontal (H)

Horizontal High

Wind Square

Termination

Wall Firestop

 

Square Termination

Vertical (V)

Horizontal (H)

32 3/4" min.

17" max.

*431/2" min.

None

541/2" min.

1 ft.

661/2" min.

2 ft.

781/2" min.

3 ft.

901/2" min.

4 ft.

*Ground Floor Corner Venting

Not to Exceed

(H) Limits

90° Elbow

30" max. 48" max. 60" max. 84" max. 20' max.

Square Termination

45° Elbow

 

Exterior Portion of

 

 

Wall

 

Wall Firestop (Round

 

Termination Only)

Firestop

 

 

 

 

 

 

 

 

 

Wall

 

Firestop

12" Minimum

45° Elbow

Figure 15 - Horizontal Termination Configuration for Corner

HorizontalInstallation Using One 90° Elbow

Round

Termination

Round Termination

(Kit 01491 Shown)

Figure 14 - Horizontal Termination Configuration for Square

and Round Terminations

10

www.desatech.com

111253-01F

Page 10
Image 10
Desa (V)V36EN-B, VV36ENC1 SERIES, VV36EPC1 SERIES Horizontal Termination Configurations, Ground Floor Installation