Pre-Installation

Preparation

Continued

Your fireplace is designed to be used in zero clearance installations. Wall or framing material can be placed directly against any exterior sur- face on the back, sides or top of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing material. See framing details on page 7.

If you plan on installing a television or enter- tainment center recessed above your fireplace, it is recommended that you maintain a minimum 18" above top of louver opening.

When locating termination cap, it is important to observe the minimum clearances shown in Figure 7, page 8.

If recessing into a wall, you can avoid extra framing by positioning your fireplace against an already existing framing member.

Do not recess termination cap into a wall or siding.

You may paint the termination cap with 450ºF (232ºC) heat-resistant paint to coordinate with the exterior finish.

There must not be any obstruction such as bushes, garden sheds, fences, decks or util- ity buildings within 24" from the front of the termination cap.

Do not locate termination cap where excessive snow or ice build up may occur. Be sure to clear vent termination area after snow falls to prevent accidental blockage of venting system. When using snow blowers, do not direct snow towards vent termination area.

Clearances

Minimum clearances to combustibles for the fire-

place are as follows:

 

*Back and sides

0"/mm

Perpendicular walls

6" (152 mm)

Floor

0"/mm

Ceiling to louver opening

42" (1067 mm)

Front

36" (914 mm)

Top of Standoffs

0"/mm

Vent

(See venting

 

instructions for specific

 

venting clearances.)

Combustible material with a maximum thick- ness of 5/8" may be flush with the top front of fireplace.

*For back and sides of fireplace, do not pack with insulation or other materials. Zero inch clearance to combustible materials are for fram- ing purpose only.

NOTICE: This fireplace is in- tended for use as supplemental heat. Use this fireplace along with your primary heating sys- tem. Do not install this fireplace as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using fireplace. This will help circulate the heat throughout the house. In the event of a power outage, you can use this fireplace as a heat source.

www.desatech.com116200-01F

Page 6
Image 6
Desa (V)VC36N, CGCDV36PR Clearances, 42 1067 mm, Front 36 914 mm Top of Standoffs Vent See venting, Venting clearances