Desa Tech CGD3924PT, CGD3930PT Installing, Continued, Floor Clearances, Combustible 14 Material

Models: CGD3924PT CGD3930PT

1 40
Download 40 pages 3.17 Kb
Page 12
Image 12
Floor Clearances

INSTALLING

Continued

_l_ ,,

Determining Minimum Mantel Clearance When Using a Hood

If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clearances shown in Figure 7 when using hood.

 

Mantel Sheff

 

 

 

 

 

 

 

Underside of

 

 

 

 

Mantel

Sheff

 

 

L

 

 

 

 

m'_m

 

 

All minimum

 

 

 

 

 

 

 

 

distances are

Minimum Non-

 

 

 

in inches

 

 

 

 

 

CombuslJble

 

 

 

Log Set

Material

12"

15"

18"

!0"<--18",

24", 30"

 

 

 

 

 

Models

 

 

r

r

Top of Fireplace

 

k

 

 

 

 

Opening

 

 

 

 

 

HOOd

Distances to

 

 

 

(GA6050, GA6052)

Underside

of

 

 

 

 

Mantel

 

 

 

Figure 7- Minimum Mantel Clearances When Using Hood

If your installation does not meet the above minimum clearances, you must:

operate the logs only with the flue damper open, OR

raise the mantel to an acceptable height, OR

remove the mantel.

Floor Clearances

A. If installing appliance on the floor level, you must maintain the minimum distance of 14" to combustibles (see Figure 8).

]

Combustible

14" Material

\\\\\\\\\1

_"_'Non-Combustible Material

Figure 8 - Minimum Fireplace Clearances ff Installed at Floor Level

B.If combustible materials are less than 14" to the fireplace, you must install appliance at least 5" above the combustible flooring (see Figure 9).

Hearth

Combustible

Matede[

Min.

Figure 9 - Minimum Fireplace Clearances Above Combustible Flooring