INSTALLING INSTALLATION AND CLEARANCES (Vent-Free Operation Only)

Continued

Maintain the minimum clearances. If you can, provide greater clear-

WARNING!

ances from floor, ceiling, and adjoining wall.

 

MINIMUM

FIREPLACE

CLEARANCE

 

TO COMBUSTIBLE

MATERIALS

Log Size

Side Wall

Ceiling

18,24,30

16

 

42"

 

LOG SIZING REQUIREMENTS

Log

Minimum Firebox

Size

 

Size

Height

Depth

Front Width

18"

17"

14"

20"

24"

17"

14 =

26"

30"

17"

14"

32"

Carefully follow the instructions below. This will ensure safe installation into a masonry, U.L. listed manufactured fireplace, or AGA design certified vent-free firebox listed for use with these models.

Minimum Wall and Ceiling Clearances (see Figure 4)

A. Clearances from the side of the fireplace opening to any combustible wall should not be less than 16 inches.

B. Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.

42"

16Left and Righti

Sides

/

/ I

Figure 4. Minimum Clearance to Well end Ceiling