INSTALLING INSTALLATION AND CLEARANCES
Continued
Maintain the minimum clearances. If you can, provide greater clear-
WARNING!
ances from floor, ceiling, and adjoining wall.
| MINIMUM | FIREPLACE | CLEARANCE |
| TO COMBUSTIBLE | MATERIALS | |
Log Size | Side Wall | Ceiling | |
18,24,30 | 16 • |
| 42" |
| LOG SIZING REQUIREMENTS | ||
Log | Minimum Firebox | Size |
|
Size | Height | Depth | Front Width |
18" | 17" | 14" | 20" |
24" | 17" | 14 = | 26" |
30" | 17" | 14" | 32" |
Carefully follow the instructions below. This will ensure safe installation into a masonry, U.L. listed manufactured fireplace, or AGA design certified
Minimum Wall and Ceiling Clearances (see Figure 4)
A. Clearances from the side of the fireplace opening to any combustible wall should not be less than 16 inches.
B. Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.
42"
16Left and Righti
Sides
/
/ I