dIXEL

 

 

 

 

Operating Instructions XWA11V

1598003200

 

 

 

 

 

 

 

+

 

 

 

 

To exit the Programming Mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

To enter a new value for the HIGH Temp ALARM (ALU).

 

 

 

HIGH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+ LOW

To enter a new value for the LOW Temp ALARM (ALL).

3.1 USE OF LEDS

Each LED function is described in the following table:

LED

MODE

Function

 

ON

ALARM signaling

 

ON

The light is on

°C

ON

Celsius degrees operation

°F

ON

Fahrenheit degrees operation

4. TEMP ALARMS SETTING

4.1HOW TO SET THE MIN TEMPERATURE ALARM

To modify the minimum (LOW) Temp ALARM: hold the + LOW keys pressed for 3 s until the minimum Temp alarm is displayed.

Change the value using the UP and DOWN keys.

Press the SET key to confirm the new value and exit.

4.2HOW TO SET THE MAX TEMPERATURE ALARM

To modify the max (HIGH) Temp ALARM: hold the + HIGH keys pressed for 3 s until the max Temp alarm is displayed.

Change the value using the UP and DOWN keys.

Press the SET key to confirm the new value and exit.

5. PROGRAMMING

5.1 HOW TO CHANGE A PARAMETER VALUE MAIN MENU

1.Enter the Programming Mode by pressing the SET and DOWN key for 3s ( and will start blinking).

2.Select the required parameter. By using the UP or DOWN KEY

3.Press the “SET” key to display its value (now only the LED is blinking).

4.Use “UP” or “DOWN” to change its value.

Press “SET” to store the new value and move to the following parameter. To exit: Press SET + UP or wait 15 s without pressing a key.

NOTE: the set value is stored even when the procedure is exited, by waiting the time-out to expire.

5.2 THE HIDDEN MENU (PR2)

The hidden menu includes all the parameters of the instrument.

5.2.1 HOW TO ENTER THE HIDDEN MENU (PR2)

1.Enter the Programming Mode by pressing the Set + down key for 3s ( and starts blinking).

2.When a parameter is displayed, release and re-pressthe SET + down for more than 7s.

3.The Pr2 label will be displayed immediately followed from the HY parameter. NOW YOU ARE IN THE

HIDDEN MENU.

4.Select the required parameter as above

5.Press the “SET” key to display its value (Now only the LED is blinking).

6.Use “UP” or “down” to change its value.

7.Press “SET” to store the new value and move to the following parameter.

To exit: Press SET + up or wait 15s without pressing a key.

NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.