dIXEL

Operating Instructions XWA11V

1598003200

 

 

 

instrument requirements. Separate the probe cables from the power supply cables, from the outputs and the power connections. Do not exceed the maximum current allowed on each relay and in case of heavier loads use a suitable external relay.

N.B. Maximum current allowed for all the loads is 15A.

8.1 PROBE CONNECTIONS

The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature. The probe can be extended up to 300 ft. Check calibration when running long lengths over 100ft.

9.USE OF THE PROGRAMMING “HOT KEY “

9.1HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)

1.Program one controller with the front keypad.

2.When the controller is ON, insert the “Hot key” and push UP key; the "uPL" message appears followed a by flashing “End”

3.Push “SET” key and the End will stop flashing.

4.Turn OFF the instrument remove the “Hot Key”, then turn it ON again.

NOTE: the “Err” message is displayed for failed programming. In this case push again o key if you want to restart the upload again or remove the “Hot key” to abort the operation.

9.2HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)

1.Turn OFF the instrument.

2.Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.

3.Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the “doL” message is blinking followed a by flashing “End”.

4.After 10 seconds the instrument will restart working with the new parameters.

5.Remove the “Hot Key”..

NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or remove the “Hot key” to abort the operation.

10. ALARM SIGNALS

Message

Mode

Cause

Outputs

“P1”

Flashing

Probe failure

Alarm output ON

“PoF”

Flashing (3s)

Keyboard locked

Not changed

“Pon”

Flashing (3s)

Keyboard un-locked

Not changed

“HA”

Alternated with temp

Maximum T° alarm

Alarm output ON;

“LA”

Alternated with temp

Minimum T° alarm

Alarm output ON;

“dA”

Alternated with temp

Door switch alarm

Alarm output ON;

“EA”

Alternated with temp

External alarm

Alarm output ON;

“PAn”

Alternated with temp

Serious external alarm

Alarm output ON;

dEF

Alternated with temp

Defrost is running

Not changed

The alarm message is displayed until the alarm condition is reset.

Silencing buzzer

Once the alarm signal is detected the buzzer can be silenced by pressing the UP key.

10.1 ALARM RECOVERY

Probe alarms : “P1” (probe1 faulty), “P2” ; they automatically stop 10s after the probe restarts normal operation. Check connections before replacing the probe.

T° alarms HA” and “LA” automatically stop as soon as the thermostat T° returns to normal values or when the defrost starts.

Door switch alarm dA” stops as soon as the door is closed.

External alarms EAL”, “BAL” stops as soon as the external digital input is disabled.