MAINTENANCE INSTRUCTIONS :
TURN OFF THE GAS WITH THE SHUTDOWN VALVE AND THE ELECTRICAL POWER BEFORE SERVICING THE APPLIANCE.
*The venting system and the gas insert should be inspected at least once a year.
*Remove the glass front and the logs clean them if necessary.
*The control compartment, air circulating passages, firebox, logs and burner should be cleaned at least once a year by vacuuming or brushing.
*Check the pilot flame to see if it is adjusted properly.
*Check the burner for flame lifting or for usual flame pattern. If necessary clean the burner orifice.
*Keep the area and the free from combustible materials, gasoline and other flammable vapors and liquids.
PILOT BURNER ADJUSTMENT :
The flame from the pilot should cover 3/8” to 1/2” of the power generator. If not, you need to do the following adjustment.
1.Remove the pilot adjustment cap on the gas valve. Depending on the valve model, the pilot adjustment screw could be indicated differently.
2.Adjust the pilot key to provide a properly sized flame.
3.Replace the pilot adjustment cap on the gas valve.