ADJUSTING AIR SHUTTER

ULTRA FLAME DV “0” Clearance Fireplace

ADJUSTING AIR SHUTTER

To adjust the air shutter there is an adjustment screw. The factory setting for the air shutter is 3/16” for natural gas, ¼” for propane. After operating the appliance for half an hour or so the flames should have turned a nice yellow colour. However, in higher altitudes you may find a smudging up of the glass after a few days. The shutter should then be adjusted open in 1/16” increments until the glass stays clear. If the flame does not turn yellow the air shutter should be closed until the flame just turns yellow. To access the shutter you need to remove the glass front, the logs and grate. Lift out the hearth surrounding the burner and the shutter will be exposed underneath.

WALL THERMOSTAT

The optional wall thermostat will automatically keep your room at an even temperature. You need to choose a convenient location for the thermostat. Remember that it should be at least 10 feet from the fireplace and away from direct radiation of the fire. Run the correct gauge wire (see table) from the valve to the thermostat and wire as shown in the diagram.

Maximum length of

thermostat wire

18 Ga

20 ft

16 Ga

30 ft

14 Ga

50 ft

12 Ga

75 ft