VENT TERMINAL, ROOF INSTALLATION

ULTRA FLAME DV “0” Clearance Fireplace

VENT TERMINAL, ROOF INSTALLATION

Roof vents are required to extend at least 3 ft. above the highest point where they pass through the roof of the building and at least 2 ft. higher than any portion within 10 feet.

Clearance between combustible wall and vent pipe must be 2" and a radiation shield must be used through the insulated wall.

If the vent terminal is more than 5 feet above the roof, use roof braces to secure the whole assembly.

OPTIONAL BLOWER INSTALLATION

See the instruction sheet included with the optional blower before proceeding with its installation.