Eaton Electrical 66103 Configuration of the JBUS/MODBUS communication parameters

Models: 66103

1 16
Download 16 pages 47.78 Kb
Page 12
Image 12
Configuration of the JBUS/MODBUS communication parameters

Configuration of the JBUS/MODBUS communication parameters

Through settings port

Connect the RS232 link to a  terminal ETHERNETManual backgroundManual background

ETHERNET

Settings/Sensor

 

 

6610266103

Connect the RS232 link to a Manual background terminal Manual background

(Microsoft Hyper terminal)

Use the cord supplied with the card

Connect the card to a computer

Use a terminal emulator such as HyperTerminalTM with these settings

Bits per second

Data bits

Stop bits

Parity

Flow control

9600

8

1

none

none

 

 

 

 

 

"Echo typed characters locally" option: disabled

 

 

Check that UPS power is on.

Type EATON (or eaton).

The main configuration menu is displayed:

EATON

NETWORK MANAGEMENT CARD 1 : Reset

2 : Network configuration

3 : Set Login Password to Default

4 : Return to Default Configuration

5 : Jbus configuration

6 : Sensor configuration

0 : Exit

Press the 5 key (Jbus configuration).

The Jbus configuration menu is displayed:

Jbus settings

1 : Display Jbus settings

2 : Modify Jbus settings

3 : Display Jbus diagnostics

4 : Reset Jbus diagnostics

5 : Return to Jbus Default Configuration

6 : Display Jbus frames

0 : Exit

12 - 34003906EN/AE

Page 12
Image 12
Eaton Electrical 66103 installation manual Configuration of the JBUS/MODBUS communication parameters