![Configuration of the JBUS/MODBUS communication parameters](/images/new-backgrounds/167194/16719423x1.webp)
Configuration of the JBUS/MODBUS communication parameters
Through settings port
ETHERNET
ETHERNET | Settings/Sensor |
| |
| 6610266103 |
Connect the RS232 link to a
terminal ![Manual background](/images/new-backgrounds/167194/16719423xi6.webp)
(Microsoft Hyper terminal)
●Use the cord supplied with the card
●Connect the card to a computer
●Use a terminal emulator such as HyperTerminalTM with these settings
Bits per second | Data bits | Stop bits | Parity | Flow control |
9600 | 8 | 1 | none | none |
|
|
|
|
|
"Echo typed characters locally" option: disabled |
|
|
●Check that UPS power is on.
●Type EATON (or eaton).
The main configuration menu is displayed:
EATON
NETWORK MANAGEMENT CARD 1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
5 : Jbus configuration
6 : Sensor configuration
0 : Exit
●Press the 5 key (Jbus configuration).
The Jbus configuration menu is displayed:
Jbus settings
1 : Display Jbus settings
2 : Modify Jbus settings
3 : Display Jbus diagnostics
4 : Reset Jbus diagnostics
5 : Return to Jbus Default Configuration
6 : Display Jbus frames
0 : Exit
12 - 34003906EN/AE