2Rotary Disconnect Switches Product Description

December 2004

Product Description

Non-fused

R & W frame, 30A – 80A, non-fusible 600V AC , suitable for use in equipment or machinery as a motor disconnect.

Manual motor controller suitable for motor disconnect, horsepower and Amp rated, load break rated, meeting requirements of CSA C22.2 No 14 CEC rule 28-602 (3) (b) and UL508 “suitable for motor disconnect.” 10 kVA short circuit rating when used in conjunction with Class J fusing.

C, V, & S Frame, 30A - 1200A, non-fusible, 600V AC, rated

250 V DC inclusive to 600A. Suitable for use as motor or industrial con- trol panel disconnects, horsepower and Amp rated, load break rated, meeting requirements of CSA C22.2 No 4 and UL98.

Fusible

30A - 800A fusible 600V AC,

C, V & F Frame, rated 250 V DC inclusive to 400A. Suitable for use as motor or industrial control panel disconnect, suitable for use as a service entrance disconnect, horse- power and Amp rated, load break rated, meeting requirements of CSA C22.2 No 4 and UL98.

Features, Benefits and Functions

Fusible and non-fusible

Rotary or toggle operation (non-fused)

Motor disconnects available approved to CEC rule 28-602(3)(b)

Base mounting or DIN rail mounting

Compact design to minimize panel space requirements

Pistol type or selector type handles for through-the-door operation.

Toggle type handle for internal panel mounting

Variable depth – complete range of shafts that can be cut for specific enclosure depths

Clear ON and OFF indication.

Padlockable in the OFF position with up to three padlocks.

Interlocked, defeatable handle avail- able. Allows access by authorized personnel in the ON position.

ON/OFF/TEST (3 position) handles allow testing of the control circuit auxiliaries without switching the main contacts.

Optional N/O, N/C auxiliary contacts available

Visible blade indication up to 200A (non-fused C & V frames)

Line side shrouds standard on all ratings for C, S, V & F frames

Load side finger shrouds standard on non-fusible 30-100A C & V frame and 30-60A fusible.

Optional shrouds available for higher ratings of V, S & F frame

Terminal lugs standard for C & V frame 30-100A non-fused and 30-60A fusible.

Standards and Certifications

R- W-Frames

UL 508

CSA C22.2 No 14 CEC rule 28-602(3)(b)

IEC 60-947-3

C-, V-, S-, F-Frames

UL 98

CSA C22.2 # 4

IEC 60-947-3

CE

Options and Accessories

Neutral modules.

Auxiliary contacts.

4th pole modules.

Protective earth modules.

C-Frame

C-Frame

V-Frame

V-Frame

Non-Fusible

Fusible

Fusible

Non-Fusible

R-Frame

W-Frame

S-Frame

F-Frame

Non-Fusible

Fusible

Non-Fusible

Non-Fusible

 

 

NOTE: Photo does not represent proportional sizing between frame types

For more information visit us at: www.eatonelectrical.ca

Page 3
Image 3
Eaton Electrical Disconnect Switches manual Product Description, Standards and Certifications, Options and Accessories