Table 16. IEC Non-Fusible/Fusible Disconnect Switches from 32 to 1250 A

Description

Catalogue Number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C362UC30

C363UV30C

C362UV60

C362UV100

C362UV200

C362US400

C362US600

C362US800

C362US1000

C362US1200

 

C362UC30CT

C363UV30J

C363UV60J

C363UV100J

C363UV200J

C363UV400J

C363UF600J

C363UF800L

 

 

 

C363UC30JT

C363UV30CT

C363UV60JT

C363UV100JT

C363UV200JT

C363UV400JT

 

 

 

 

 

 

C363UV30JT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rating Ampere

32

32

63

100

200

400

600/630

800

1000

1250

 

 

 

 

 

 

 

 

 

 

 

Rated Insulation

800

750

750

750

750

1000

1000

1000

1000

1000

Voltage Ui (V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Impulse

8 kV

8 kV

8 kV

8 kV

8 kV

12 kV / 8 kV

12 kV

12 kV

12 kV

12 kV

Voltage (Uimp)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Current (A)

 

 

 

 

 

 

 

 

 

 

400 V AC – AC 22A

32

32

63

100

200

400

630

800

1000

1200

– AC 23A

32

32

63

100

200

400

630

800

1000

1000

 

 

 

 

 

 

 

 

 

 

 

690 V AC – AC 22A

32

32

63

100

200

400

500/630

630/800

630

630

– AC 23A

32

32

63

100

200

200/250

200/630

400/630

400

400

 

 

 

 

 

 

 

 

 

 

 

Motor Power (kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400 V AC – AC 23A

15

15

30

51

100

220

355

450

560

560

 

 

 

 

 

 

 

 

 

 

 

500 V AC – AC 23A

18.5

18.5

40

63

140

280

450

560

560

560

 

 

 

 

 

 

 

 

 

 

 

690 V AC – AC 23A

25

25

55

90

185

185/220

185/600

400/600

400

400

 

 

 

 

 

 

 

 

 

 

 

Maxi. peak let through

5.5

7.6

17.6

17.6/22

32

48/36

48/77

75/77

75

75

current (kA peak)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Cu

6

6

10

25

50

185

2 x 150

2 x 185

2 x 240

––––

Cable Section (mm2)

 

 

 

 

 

 

 

 

 

 

Minimum Cu

––––

––––

––––

–––

––––

––––

2 x 30 x 5

2 x 40 x 5

2 x 50 x 5

2 x 60 x 5

Busbar Section (mm2)

 

 

 

 

 

 

 

 

 

 

Value on left = non-fusible/ value on right = fusible.

Cable vs busbar connection on fusible @ 630A.

Busbar vs cable connection on fusible @ 800A.

For more information visit us at: www.eatonelectrical.ca

Page 18