Elk M1KPAS Troubleshooting and Diagnostics, Symptom, Potential Cause, Remedy Things to try

Models: M1KPAS

1 6
Download 6 pages 60.19 Kb
Page 4
Image 4
Troubleshooting and Diagnostics

Troubleshooting and Diagnostics

Symptom

Potential Cause

Remedy (Things to try)

No visual or audible feedback

Keypad is not communicating with the

Check wiring and plug connections. Verify power at

when buttons are pressed.

control. Power may be off or wiring

connections using a voltmeter.

 

unplugged.

 

 

 

 

Ready, Trouble, Armed, Stay, and

Keypad is communicating but it has not

Use the bus module enrollment procedure to enroll the

Exit LEDs are lighting in a

been enrolled with the Control.

keypad into the Control.

clockwize rotation.

 

 

 

 

 

Numeric keys All Flashing

Keypad is in the Setup Mode is waiting for

Refer to the instructions for address setting OR press the

 

an address setting.

Exit key to return to regular operation.

 

 

 

Erratic operation. LEDs and

Improper data bus termination, improper

Check for: a. Reversed data bus wires. b. Improper data

buttons do not seem to be

wiring or wiring, OR another keypad already

bus termination (see manual). c. Duplicate address

responding properly.

exists at this data bus address.

"conflict" with another keypad. If all else fails swap with

 

 

another keypad making sure to re-address and re-enroll. If

 

 

problem goes away the old keypad may be defective. If

 

 

problem persists contact Tech Support.

 

 

 

Please Note: The back page of this booklet is designed so that it may be separated from the rest of the pages. It may then be folded in half to convert into a User Operation Guide for the M1KPAS Arming Station. It may be placed inside or with the regular M1/EZ8 User Guide book as a suppliment to those complete instructions.