Refrigerant Connections
21 Liebert® CRV
Figure 16 Pipeline air conditioner - condenser

6.2.2 Pipe Diameter and Thickness

!
WARNING
Risk of explosive discharge. Can cause equipment damage, injury or death.
Use only Type ACR copper tubing sized per Tables 7,8,9 and 10 for pipes connecting the
Liebert CRV and the condensing unit.
Table 7 Piping and refrigerant sizes for Liebert Lee-Temp condensers with R-410A
Condenser Piping Connection Sizes
Condenser Connections, O.D., in.
Liebert Lee-Temp
Size, in. (mm)
Liebert Lee-Temp Connections, I.D., in.
Condenser Model # Hot Gas Liquid
Hot Gas
Tee
Liquid To
L-T Valve
Receiver
Out
DCSL28K 1-1/8 7/8 9 x 36 (229 x 914) 1-1/8 5/8 7/8
DCSL60K 1-1/8 7/8 11 x 36 (279 x 914) 1-1/8 5/8 7/8
DCSL90K 1-1/8 7/8 11 x 48 (279 x 1219) 1-1/8 5/8 7/8
Source: DPN001623, Rev. 6, Page 3
Table 8 Recommended refrigerant line sizes for Liebert Lee-Temp condensers with R-410A Cu, OD
Liebert CRV Model #
Total Equivalent
Length, ft. (m)
Hot Gas Line,
in. (mm)
Liquid Line,
in. (mm)
CR020RA
50 (15.2) 3/4 (19.1) 5/8 (15.9)
100 (30.5) 3/4 (19.1) 5/8 (15.9)
150 (45.7) 3/4 (19.1) 5/8 (15.9)
300 (91.4) 7/8 (22.2)* 3/4 (19.1)
CR035RA
50 (15.2) 7/8 (2 2.2) 3/4 (19.1)
100 (30.5) 7/8 (22.2) 3/4 (19.1)
150 (45.7) 7/8 (22.2) 3/4 (19.1)
300 (91.4) 1-1/8 (28.6)* 7/8 (22.2)
Consult factory for proper line sizing for runs longer than 300 ft. (91.4m) equivalent length.
* Must downsize vertical riser one trade size (1-1/8” to 7/8” or 7/8” to 3/4”).
Source: DPN001623, Rev. 6, Page 3

B

C

CDT
COND
A
(Distance) D = A + B + C
CDT = Conditioner
COND = Condenser