Operating Instructions

Set Date/Time: Allows user to enable/disable DST (Daylight Saving Time), change the Day, Date and Time setting on Nfinity. When enabled, the time will automatically adjust to Daylight Saving Time.

Set Time/Date

DST Mode

Set Time/Date

DST Mode

DST Mode

Enabled

* Disabled

Set Date/Time

Date/Time

MM/DD/YYYY HH:MM:SS

Max Load Alarm Set: Allows an alarm to set when Nfinity’s load reaches a specific level.

Max Load Alarm Set

Mode

Threshold

Alarm Mode

Max Load Alarm Mode

*Enable Disable

Threshold

Max Load Alarm Set

Threshold kVA = xx.x

UPS Shutdown Delay: Delays UPS shutdown for specified amount of time after receiving shutdown command via relay contacts only.

UPS Shutdown Delay xxx seconds

Redundant Alarm Set: Sets Alarm to notify user when redundancy is no longer available.

Redundant PWR Alarm Set

Enable

* Disable

Service Contact: Set a contact for the user to reach if problems occur.

Service Contact

>Company Name

Company Phone

Company Name

Company/Name

LIEBERT CORP.

Phone Number

Phone Number

WWW.LIEBERT.COM

Remote Shutdown: Enables / Disables the Remote Communications Shutdown.

If you are using MultiLink™ software, this parameter should be enabled in order for the UPS output to be turned off once the operating system has been shut- down.

Remote Shutdn

*Enable Disable

External Battery: Sets total amp-hour for external batteries to provide a more accurate runtime remain- ing value on the LCD display and through communi- cations.

External Battery

Amp-hour

> Charge Current

External Batt Config Enter total amp-hour

0000

External Batt Config Enter charge current

00.0

When using the Non-Modular External Battery Cabinets with Chargers (P/N: PB10SLF105WC120), enter the following:

# Cabinets

AH Value

Charge Current

1

0091

07.0

2

0182

14.0

3

0273

21.0

4

0364

28.0

5

0455

35.0

6

0546

42.0

25

Page 29
Image 29
Emerson 240V, 208 user manual DST Mode, Set Date/Time, Alarm Mode, Threshold, Company Name, Phone Number