Split System Models
7.6Water and
For installation guidelines, refer to Installing the Indoor Condensing Unit on page 65.
7.6.1Piping Considerations
It is recommended that manual service
When the water source for the condenser is of poor quality, it is good practice to provide cleanable fil- ters in the supply line. These filters will trap the particles in the water supply and extend the service life of the
3-Ton Connection Sizes
Condenser Water Inlet | 7/8" OD Cu |
Condenser Water Outlet | 7/8" OD Cu |
Suction Line | |
Liquid Line: | 5/8 - 18 male #6 quick connect |
| |
Condenser Water Inlet | |
Condenser Water Outlet | |
Suction Line | |
Liquid Line |
Table 32 Water and
| Net Weight, | Glycol Volume, | |
Model | lb (kg) | gal (l) | |
|
|
| |
MC_44W | 200 (91) | 1.7 (6.4) | |
MC_43W | |||
|
| ||
MC_69W | 282 (128) | 2.0 (7.6) | |
MC_68W | |||
|
|
7.6.2Condenser Water Requirements
The standard maximum water pressure is 150 psig (1034 kPa). For applications above this pressure, consult the factory about high pressure systems.
The system will operate in conjunction with a cooling tower, city water, or drycooler.
7.6.3Regulating Valve
For details, refer to sections 4.3.1 - Standard Valve - 150psig (1034kPa) System for 3 &
Units (Johnson Controls Valve) High Pressure Valve - 350psig (2413kPa) System for
72