Installation (Applicable to all Models)
2.5.2Humidifier Supply Water—Optional Infrared
•1/4" supply line; maximum water pressure is 150 psi (1034kPa)
•Size humidifier supply line for 1 gpm (3.8 l/m), with a minimum water pressure of 20 psi (138kPa)
•Do not supply
2.6Facility Fluid and Piping Maintenance
Facility water and glycol quality remain a requirement throughout the life of the piping system. Fluid and piping system maintenance schedules must be established and performed. A local fluid mainte- nance program must be established that will evaluate fluid chemistry and apply necessary treatment. A periodic leak inspection of facility and unit fluid piping is recommended. Refer to 5.4 - Glycol Pip- ing.
2.7Electrical Connections
A manual electrical disconnect switch should be installed within 5 feet (1.6 m) of the unit in accor- dance with codes, or a
! WARNING
Risk of electric shock. Can cause injury or death.
Potentially lethal voltages exist within this equipment during operation. Observe all cautions and warnings on unit and in this manual.
The Liebert iCOM microprocessor does not isolate power from the unit, even in the “Unit Off” mode. The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic.
NOTICE
Risk of improper scroll compressor installation. Could cause poor performance and compressor damage.
18