Emerson 3000 installation manual 5.5.3Filling the System, Ethylene glycol concentrations

Models: 3000

1 88
Download 88 pages 36.41 Kb
Page 52
Image 52
Table 16 Ethylene glycol concentrations

Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor

Table 16 Ethylene glycol concentrations

% Glycol by Volume

0 *

10

20

30

40

50

Freezing Point °F (°C)

32 (0)

25 (-3.9)

16 (-8.9)

5 (-15.0)

-10 (-23.3)

-32 (-35.5)

Apparent Specific Gravity

1

1.014

1.028

1.042

1.057

1.071

@ 50°F (10°C)

 

 

 

 

 

 

* A minimal amount of glycol should be considered for inhibitive coil protection.

NOTICE

Risk of corrosion from water impurities. Can cause equipment damage.

The quality of water used for dilution must be considered because water may contain corrosive elements which reduce the effectiveness of the inhibited formulation. Water that is classified as soft (low in chloride and sulfate ion content less than 100 parts per million each) should be used.

5.5.3Filling the System

Installation of hose bibs at the lowest point of the system is recommended. When filling a glycol sys- tem keep air to a minimum. Air in glycol turns to foam and is difficult and time-consuming to remove. (Anti-foam additives are available and may be considered.) Open all operating systems to the loop.

With the top vent(s) open, fill the system from the bottom of the loop. This will allow the glycol to push the air out of the top of the system, minimizing trapped air. Fill to approximately 80% of calcu- lated capacity. Fill slowly from this point, checking fluid levels until full.

NOTE

For glycol solution preparation and periodic testing, follow manufacturer's recommendations. Do not mix products of different manufacturers.

46

Page 52
Image 52
Emerson 3000 installation manual 5.5.3Filling the System, Ethylene glycol concentrations