DPN000352 Rev. 01
Liquid Refrigerant Line
3/8" OD CU on Models BU042A/BU040A 1/2" OD CU on Models BU067A/BU065A
Piping outlet locations through the plenum are the same as the unit. See below for descriptions and connection sizes.
Hot Water Return 5/8" OD CU (optional)
Hot Water Supply 5/8" OD CU (optional)
Liebert iCOM Control
PIPING OUTLET LOCATIONS (See Cabinet and Floor Planning Dimensional Data for Piping Opening Sizes.)
Installation (Applicable to all Models)
Figure 5 Piping connections for
Humidifier Water Supply Line 1/4" OD CU
Hot Gas Refrigerant Line 5/8" OD CU on Models BU042A/BU040A
7/8" OD CU on Models BU067A/BU065A
Condensate Pump Line 1/2" OD CU
Used only if optional condensate
pump is ordered.
Condensate Drain 3/4" FPT
Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without a condensate pump have a