Humidifier Water Supply Line 1/4" OD CU
DPN000352 Rev. 01
Liquid Refrigerant Line
3/8" OD CU on Models BU042A/BU040A 1/2" OD CU on Models BU067A/BU065A
Piping outlet locations through the plenum are the same as the unit. See below for descriptions and connection sizes.
Hot Water Return 5/8" OD CU (optional)
Hot Water Supply 5/8" OD CU (optional)
Liebert iCOM Control
PIPING OUTLET LOCATIONS (See Cabinet and Floor Planning Dimensional Data for Piping Opening Sizes.)
Installation (Applicable to all Models)

Figure 5 Piping connections for air-cooled units - Upflow models

Humidifier Water Supply Line 1/4" OD CU

Hot Gas Refrigerant Line Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background 5/8" OD CU on Models BU042A/BU040A

7/8" OD CU on Models BU067A/BU065A

Condensate Pump Line Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background 1/2" OD CUManual backgroundManual background Used only if optional condensate Manual backgroundManual backgroundManual backgroundManual background pump is ordered.Manual backgroundManual backgroundManual backgroundManual backgroundManual background

Condensate Drain 3/4" FPT

Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without a condensate pump have a factory-supplied trap in the unit, so a field trap should not be added. Units with a condensate pump will require a field-supplied trap downstream from the pump.The drain line must comply with all applicable codes. (If condensate pump is ordered piping is out top of unit).

11