Installation (Applicable to all Models)
Figure 7 Piping connections for split system fan coil units - Upflow models
Humidifier Water Supply Line 1/4" OD CU
Suction Refrigerant Line #11 Quick Connect on Models BU036E/BU035E
1 1/8" OD CU on Models BU060E/BU059E Condensate Pump Line
1/2" OD CU; used only
if optional condensate pump is ordered.
Piping outlet locations through the plenum are the same as the unit. See below for descriptions and connection sizes.
Hot Water Return
5/8" OD CU (optional)
Liquid Refrigerant Line
#6 Quick Connect on Models BU036E/BU035E
1/2" OD CU on Models BU060E/BU059E
Hot Water Supply
5/8" OD CU (optional)
iCOM Control
Panel
Condensate Drain; 3/4" FPT
PIPING OUTLET LOCATIONS (See Cabinet and Floor Planning Dimensional Data for Piping Opening Sizes.)