Installation (Applicable to all Models)
Figure 8 Piping connections for water/glycol and GLYCOOL units - Downflow models
iCOM Control
Panel
Condensate Drain 3/4" FPT
Field pitch a minimum
of 1/8" (3.2mm) per ft. (305mm). The drain line must comply with all applicable codes
Humidifier Water Supply Line 1/4" OD CU
Condenser Supply Line
7/8" OD CU on Models BF046WG/BF045WG
Condenser Return Line
7/8" OD CU on Models BF046WG/BF045WG
Hot Water Return
5/8" OD CU (optional)
Hot Water Supply
5/8" OD CU (optional)
PIPING OUTLET LOCATIONS (See Cabinet and Floor Planning Dimensional Data for Piping Opening Sizes.)
DPN000364 Rev. 01
14