Emerson 3000 installation manual DPN000207, Rev0

Models: 3000

1 88
Download 88 pages 36.41 Kb
Page 74
Image 74
DPN000207

Split System Models

Figure 37 3-ton centrifugal air-cooled condensing unit (con't.)

Field-supplied unit disconnect switch when optional disconnect is not provided in unit

Single- or three-phase

electric service not by Liebert

Field-supplied 24V

 

NEC Class 2 wiring

Factory-wired

to fan/coil unit

 

to components

 

on electric panel

Optional factory-installed

Line voltage electric power disconnect switch supply conduit entrance

Single- or three-phase

electric service not by Liebert

Connection terminal Rev0Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background for field-suppliedManual backgroundManual backgroundManual backgroundManual background grounding wireManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Low-voltage electric power supply entrance

Heat rejection connection.

Field-supplied 24V NEC

Class 2 wiring. See NOTE 2.

Wire connections from evaporator

 

 

DPN000207

 

 

mod:

 

 

Rev0

1.

24V ground

 

 

 

2.

24V supply

NOTES:

3.

High-pressure alarm (optional)

4.

Hot gas bypass connection

1.

Refer to specification sheet for full load amp. and wire size amp. ratings.

 

(only on units with hot gas

2.

Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75' (23m)

 

bypass)

 

or not to exceed 1 volt drop in control line.

68

Page 74
Image 74
Emerson 3000 installation manual DPN000207, Rev0