Emerson 3000 installation manual Unit refrigerant charge

Models: 3000

1 88
Download 88 pages 36.41 Kb
Page 64
Image 64
Table 21 Unit refrigerant charge

Split System Models

Refrigerant charge requirements: Total refrigerant charge will be required only if units are evacuated during installation or maintenance. Total refrigerant charge = evaporator + lines + condensing unit.

NOTE

All condensing units and 3-ton evaporator units are fully charged with refrigerant. All 5 ton evaporator units include a nitrogen holding charge only. See Table 21 for field charge required. If field-supplied refrigerant piping is installed, refrigerant must be added to the system.

Once all piping is complete, check for leaks and dehydrate the field piping as follows:

1.Pressurize the field piping to 150 PSIG (1034 kPa) using dry nitrogen with a trace of refrigerant. Check system for leaks with a suitable leak detector.

2.After completion of leak testing, release the test pressure (per local code) and pull a deep vacuum on the field piping with a suitable pump.

3.After 15 minutes, check the pressure readings and, if they have not changed, break vacuum with dry nitrogen. Pull a second vacuum to 250 microns or less. Recheck the pressure after 15 minutes.

Table 21 Unit refrigerant charge

 

R407C Charge

Model

 

lb (kg)

 

 

 

BF/BU 036E

0.5

(0.2)

 

 

 

BF/BU 035E

0.5

(0.2)

 

 

 

BF/BU 060E

0.8

(0.4)

 

 

 

BF/BU 059E

0.8

(0.4)

 

 

MC_40/39A

12.9 (5.8)

 

 

 

MC_65/64A

26.1

(11.8)

 

 

PF_042A-_L

12.9 (5.8)

 

 

PF_041A-_L

12.9 (5.8)

 

 

 

PF_Z42A-_L

25.8

(11.7)

 

 

 

PF_Z41A-_L

25.8

(11.7)

 

 

 

 

R407C Charge

Model

 

lb (kg)

 

 

 

PF_042A-_H

25.8

(11.7)

 

 

 

PF_041A-_H

25.8

(11.7)

 

 

 

PF_067A-_L

25.8

(11.7)

 

 

 

PF_066A-_L

25.8

(11.7)

 

 

 

PF_Z67A-_L

50.1

(22.7)

 

 

 

PF_Z66A-_L

50.1

(22.7)

 

 

 

PF_067A-_H

50.1

(22.7)

 

 

 

PF_066A-_H

50.1

(22.7)

 

 

 

MC_44/43W

3.4

(1.5)

 

 

 

MC_69/68W

5.9

(2.7)

 

 

 

Table 22 Line charges - refrigerant per 100 ft. (30 m) of Type “L” copper tube

 

 

R407C

 

 

 

 

Liquid Line

Suction Line

O.D.

lb (kg)

lb (kg)

1/2"

7.3

(3.3)

-

 

 

 

5/8"

11.7 (5.3)

0.4 (0.2)

 

 

 

 

7/8"

24.4

(11.1)

1.0 (0.4)

 

 

 

 

1-1/8"

41.6

(18.9)

1.7 (0.7)

 

 

 

 

1-3/8"

63.3

(28.7)

2.7 (1.1)

 

 

 

 

Table 23 Recommended refrigerant lines (R407C) sizes OD copper

 

3.5-Ton

5-Ton

 

 

036E (035E)

060E (059E)

Equivalent Feet (m)

 

 

 

 

 

Suction

Liquid

Suction

 

Liquid

 

 

 

 

 

 

0-50 (0-15)

7/8"

1/2"

1-1/8"

 

1/2"

 

 

 

 

 

 

51-100 (16-30)

1-1/8"

1/2"

1-1/8"

 

5/8"

 

 

 

 

 

 

101-150 (31-45)

1-1/8"

5/8"

1-3/8"

 

5/8"

 

 

 

 

 

 

58

Page 64
Image 64
Emerson 3000 installation manual Unit refrigerant charge