Emerson 3000 Liebert Lee-TempPiping, Liebert Lee-TempControlled Materials Supplied

Models: 3000

1 88
Download 88 pages 36.41 Kb
Page 37
Image 37
Liebert Lee-Temp Piping

Air-Cooled Models—Self-Contained Compressor

3.5Air-Cooled Condenser with Liebert Lee-Temp “Flooded Condenser” Head Pressure Control System

The Liebert Lee-Temp system consists of a modulating type head pressure control valve and insulated receivers with heater pads to ensure operation at ambient temperatures as low as -30°F (-34.4°C). The Liebert Lee-Temp system can be used with any compressor choice.

Liebert Lee-Temp Piping

A discharge line and a liquid line must be field-installed between the indoor unit and the outdoor con- denser. See Figures 17 and 18 for details.

Liebert Lee-Temp Controlled Materials Supplied

Built-in, pre-wired condenser control box

Air-Cooled condenser

Piping access cover to be reinstalled when piping is complete (models with one to four fans only)

Bolts—four per leg (3/8" x 5/8")

Terminal block for two-wire, 24V interlock connection between unit and condenser

Condenser legs—four with 1-fan, six on two-, three- and six-fan models and eight on four- and eight-fan models

Bolts—six per receiver (3/8" x 1")

Lee-Temp system:

Insulated storage receiver

Head pressure control valve with integral check valve

Service valve

Pressure relief valve

Liquid level sight glass

Check valve

NOTE

Lee-Temp heater pads require a separate, continuous electrical source. See nameplate on unit for proper voltage.

Lee-Temp Leak Check and Evacuation Procedure

Proper leak check and evacuation can be accomplished only with all system solenoid valves open and check valves accounted for.

NOTE

Systems with scroll or digital scroll compressors include a factory-installed check valve and an additional downstream Schrader valve with core in the compressor discharge line. Proper evacuation of the condenser side of the compressor can be accomplished only using the downstream Schrader valve. See piping schematic (Figure 18).

1.If unit power is available, open the unit liquid line solenoid valves using the evacuation function in the diagnostic section of the Liebert iCOM control. If unit power is not available, a field- supplied 24VAC / 75VA power source must be directly connected to each of the unit solenoid valves.

2.Attach a jumper hose from the service valve fitting on the outlet of the receiver and the Schrader fitting on the discharge header of the condenser. Front-seat the service valve approximately two (2) turns.

3.For scroll and digital scroll compressors, connect refrigerant gauges to the suction rotalock valves and discharge line Schrader valves (see Note above).

4.Open the service valves and place a 150 PSIG (1034 kPa) of dry nitrogen with a tracer of refrigerant. Check system for leaks with a suitable leak detector.

5.After completion of leak testing, release the test pressure (per local code) and pull an initial deep vacuum on the system with a suitable pump.

31

Page 37
Image 37
Emerson 3000 installation manual Liebert Lee-TempPiping, Liebert Lee-TempControlled Materials Supplied