BYPASSING & ISOLATING (continued)
RETURN TO SERVICE
This procedure explains how to return the automatic transfer switch (ATS) to service after inspection and maintenance. Observe the Bypass Switch Position indica- tor and lights).
1.Use the two tab handles to roll the transfer switch into the enclosure (isolation contacts facing inward) until the crank bearings stop against the
tab
handles
left rail | right rail |
|
Figure
and pulled out for inspection.
Close the enclosure door to prevent personal
injury in case of electrical system fault.
2.Turn Isolation Handle clockwise (approx. 6 turns) until the window shows TEST and TS TEST light comes on.
Bypass Switch | E |
Turn crank |
|
clockwise |
|
until | L |
window |
|
shows |
|
TEST. |
|
| N |
Automatic Transfer Switch |
|
Figure |
TS CONNECTED
Middle amber light |
|
should come on. | TS TEST |
| |
| TS ISOLATED |
position | TEST | clockwise – draws in | |
window | the transfer switch | ||
|
Figure
3.The ATS can be tested now without load interruption (see page
Solenoid interlock prevents you from closing the isolation contacts until the ATS is in the same position as the Bypass Switch.
4.Observe which Bypass Switch Position window indica- tor is yellow (NORMAL or EMERGENCY) at the Bypass Switch Handle. This indicates the source connected to the load.
5.Observe which Transfer Switch Connected To light is on (Normal or Emergency) on the door. This is the position of the Transfer Switch. If it is not in the same position as the Bypass Handle change the position of the Transfer Switch as follows:
To change the position of transfer switch
Operate to NORMAL | Operate to EMERGENCY |
Turn Transfer Control | Turn Transfer Control |
switch to Retransfer | switch to Transfer Test |
Delay Bypass. | (hold 15 seconds).* |
|
|
Connected To Normal | Connected To Emergency |
light should come on. | light should comes on. |
|
|
*If Feature 2B time delay is used, there will be a delay before transfer to Emergency.
NOTE: With Normal available, the automatic transfer switch will not stay in the emergency position unless Feature 3A time delay is used (at least 30 seconds).