Emerson 7ADTB manual BYPASSING & ISOLATING continued, To Bypass Normal Source

Models: 7ADTB

1 17
Download 17 pages 26.2 Kb
Page 11
Image 11
BYPASSING & ISOLATING (continued)

BYPASSING & ISOLATING (continued)

To Bypass Normal Source*

(Load connected to Normal Source)

The Transfer Switch Connected To Normal light is on and Transfer Switch Connected To Emergency light is off.

Push in the handle and turn it counterclockwise.*

Push in* the Bypass Handle all the way, then turn it counterclockwise until Bypass Switch Position shows closed on NORMAL (yellow window indicator). The green light Bypassed to Normal will come on and the amber light Not In Automatic will flash.

Push in

Bypass Switch

E

Bypass

 

 

Handle

 

 

and

 

 

turn it

 

 

counter-

 

L

clockwise.

 

 

 

 

 

N

 

ATS

 

Figure 3–5. Bypass to Normal diagram.

BYPASS SWITCH

Upper green

BYPASSED TO NORMAL

light comes on

 

BYPASSED TO EMERGENCY

To Bypass Emergency Source*

(Load connected to Emergency Source)

The Transfer Switch Connected To Emergency light is on and Transfer Switch Connected To Normal light is off.

Turn the handle clockwise.*

Turn* the Bypass Handle clockwise until Bypass Switch Position shows closed on EMERGENCY (yellow window indicator). The red light Bypassed to Emergency will come on and the amber light Not In Automatic will flash.

Turn

Bypass Switch

E

 

 

Bypass

 

 

Handle

 

 

clock-

 

 

wise.

 

L

 

 

 

 

N

 

ATS

 

Figure 3–7. Bypass to Emergency diagram.

BYPASS SWITCH

BYPASSED TO NORMAL

Lower red light comes on

BYPASSED TO EMERGENCY

Lower window indicator NORMAL shows yellow

Upper window indicator To Bypass Normal Source* EMERGENCY shows yellow

Figure 3–6. Status light and window indicator for

Figure 3–8. Status light and window indicator for

Bypassed to Normal Source.

Bypassed to Emergency Source.

The automatic transfer switch can now be put in the TEST or OPEN position. See ISOLATING on page 3–3.

*NOTE: When Accessory 40*B (reversed Normal & Emergency connections) is specified, the handle operation is reversed. Follow instructions on the door.

3---2

Page 11
Image 11
Emerson 7ADTB manual BYPASSING & ISOLATING continued, To Bypass Normal Source, To Bypass Emergency Source