BYPASSING & ISOLATING (continued)

Do not close the isolation contacts unless the Transfer Switch (ATS) and Bypass Switch are in the same position!

6.When the transfer switch is in the same position as the Bypass Switch handle, continue turning the Isolation Handle clockwise (about 8 turns) until the window shows CONN (connected).

Bypass Switch

E

Turn crank

 

clockwise

L

until

 

window

 

shows

 

TEST.

 

 

N

Automatic Transfer

Switch

Figure 3–18. TEST to CONN (connected) position.

Upper amber light should be on.

TS CONNECTED

TS TEST

TS ISOLATED

position

CONN

clockwise – draws in

window

the transfer switch

 

Figure 3–19. Isolation Handle turned to CONN.

3---6

Page 15
Image 15