Installation and Configuration

5.0INSTALLATION AND CONFIGURATION

Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 6.0 - Initial Start-Up and Electrical Checks.

Visually inspect the UPS for freight damage. Report any damage to the carrier and your local dealer or Liebert representative.

! CAUTION

The UPS is heavy (see 13.0 - Specifications). Take proper precautions when lifting or moving it.

Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it where air flows unrestricted around the unit. The installation location must be free of water, flam- mable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of

4 inches (100mm) in the front and rear of the UPS. Maintain an ambient temperature range of 32-104°F (0 to 40°C).

NOTE

UPS operation in sustained temperatures above 77°F (25°C) reduces battery life.

5.1Install the Main Cabinet

The GXT2-6000RTL630 may be installed in either a tower configuration or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instructions in either 5.1.1 - Tower UPS Installation or 5.1.2 - Rack-Mount UPS Installation.

5.1.1Tower UPS Installation

When using the GXT2-6000RTL630 in a tower configuration, use the included support base (shown below, left) to stabilize the UPS. If any external battery cabinets are added, they will include spacers to accommodate the additional cabinets (shown below, right).

Attach Bezels to Top

When used as a tower, the GXT2-6000RTL630 requires bezels attached to the top. To connect the bezels:

1.Position the UPS so that the battery compartments are on the right side.

2.Attach the top bezels by placing them on the mounting holes and sliding them toward the rear of the UPS.

Figure 5 Tower-use support bases, spacers for external battery cabinets

3U

3U

2U

2U

5U support base for GXT2

Spacers added to support base

End bases and 3U spacer

to accommodate additional battery cabinets

11