Specifications

Table 7

Internal battery specifications

 

 

 

 

 

 

Model Number

 

GXT2-240BATKIT

 

 

 

Dimensions, W x D x H, in. (mm)

 

 

 

 

 

Shipping

 

21.2 x 12.2 x 16.2 (539 x 311 x 412)

 

 

 

Weight, lb (kg)

 

 

 

 

 

Unit

 

44.5 (20.2) each, (2 required)

 

 

 

 

 

Shipping

 

93.9 (42.6), (2 batteries in a single carton

 

 

 

 

 

Type

 

Valve-regulated, non-spillable, lead acid

 

 

 

 

 

Quantity x V

 

20 x 12V

 

 

 

 

 

Battery Mfr. / Part #

 

Yuasa / REW 28-12FT

 

 

 

Electrical Characteristics

 

 

 

 

 

Back-up Time

 

See Table 5 - Battery run times

 

 

 

 

 

Recharge Time

 

3 hrs. to 90% capacity after full discharge into 100% load

 

 

 

 

Table 8

Output distribution specifications

 

 

 

 

Model Number

PD-L630

 

 

Dimensions, W x D x H, in. (mm)

 

 

 

 

 

Unit

5.3 x 6.9 x 3.5 (134 x 175 x 88)

 

 

 

 

Shipping

8.9 x 10.4 x 12.4 (225 x 265 x 315)

 

 

Weight, lb (kg)

 

 

 

 

 

Unit

30 (13.5)

 

 

 

 

Shipping

33 (15)

 

 

Electrical Specifications

 

 

 

 

 

Amp Rating

24 Amps

 

 

 

 

Input Power Connections

L6-30P on 10-foot (3m) cord

 

 

 

Output Power Connection: L1-L2-G

(2) L6-30R on a 12" (300mm) cord

(2) L6-20R on a 12" (300mm) cord

 

 