Emerson GXT2-6000RTL630 user manual AC Power Connections, Disconnect, Captive, Rear View

Models: GXT2-6000RTL630

1 44
Download 44 pages 51.01 Kb
Page 33
Image 33

Maintenance

11.2AC Power Connections

Power connections may be disconnected from the UPS cabinet via a removable distribution box. This may be a convenient feature if the UPS must be moved a short distance or replaced. This box allows power connections to be conveniently disconnection from the main UPS cabinet. A label is attached to the UPS to describe these procedures.

11.2.1Disconnect

1.DO NOT turn off the branch circuit breaker feeding power the box unless you intend to disconnect all power to the load.

2.Ensure that the Maintenance Bypass Lamp is ON.

3.Switch to the maintenance bypass position.

The load is now unprotected from line disturbances or interruptions.

4.Turn off the UPS using the front panel controls.

a.If needed, push the OFF button for one second once to transfer the load to bypass.

b.Press the OFF button twice within four seconds to turn the UPS off.

5.Turn off the UPS input circuit breaker on the box at the rear of the UPS.

This input circuit breaker cuts off power only from the connector between the box and UPS. The input circuit breaker does not cut off power from the manual bypass switch.

6.Turn off the output circuit breaker on the rear of the UPS.

7.Remove the distribution box from the UPS

a.Loosen all three captive screws until the box releases.

b.Pull box away from the UPS and set the box aside on a padded surface.

8.Loosen the cover over the electrical connections by backing out the three screws one turn each.

9.Slide the cover over the electrical connections.

10.Gently retighten the three screws loosened in Step 8.

Whenever the power distribution box is not attached to the UPS, the cover must be slid over the electrical connections to prevent damage or injury.

! CAUTION

Power is still passing through the power distribution box from the utility supply to the load.

Figure 8 Power distribution box, PD-L630

REMOVE SCREWS

COVER COMMUNICATION

 

CONNECTOR PROTECTIVE COVER DO NOT

PRIOR TO INSTALLATION OF BOX ON UPS -LOOSEN THREE SCREWS 1 TURN - SLIDE COVER TO EXPOSE CONNECTOR -TIGHTEN SCREWS GENTLY UPON REMOVAL OF BOX FROM UPS -LOOSEN THREE SCREWS 1 TURN -SLIDE COVER TO REACH END SCREW AND

-TIGHTEN SCREWS GENTLY

Maintenance

Maintenance

Bypass Switch

Bypass Lamps

 

AVA

PS

BYPAS

 

AVAILABLE

Protective

 

 

 

UPS

UTILITY

Cover Over

ON

 

 

 

 

Connectors

OUTPUT

ON

 

 

 

 

BREAKER

~/T

OUTPUT

 

 

20A 240V

 

BREAKER

 

 

OFF

 

20A

240V~/T

 

 

OFF

 

 

 

 

 

 

 

Captive

Screws

BREAKER 30A

 

 

 

INPPUT

(attach

 

OFF

MANUAL BYPASS SWITCH. TO

 

 

ON

 

 

 

 

 

OUTPUT ONLY CB

DOES NOT

 

 

 

CONNECT BY

 

box to

 

 

 

PASS POWER

 

 

 

 

 

UPS)

Rear View

Front View

29

DISCONTINUED

 

PRODUCT

Page 33
Image 33
Emerson GXT2-6000RTL630 user manual AC Power Connections, Disconnect, Captive, Rear View