Emerson GXT2-6000RTL630 Troubleshooting, Indicator meanings, LED status Diagnosis/Audible alarm

Models: GXT2-6000RTL630

1 44
Download 44 pages 51.01 Kb
Page 35
Image 35

Troubleshooting

12.0TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the GXT2-6000RTL630 develops a problem. Use this information to determine whether external factors caused the problem and how to remedy the situation.

1.The Fault indicator will illuminate, indicating the UPS detected a problem.

2.An alarm will sound, alerting that the UPS requires attention.

Fault

Example shows UPS on bypass because of output overload, signified by amber load indicator.

AC INPUT BA

 

 

 

 

 

 

ON BYPASS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.3. One or more additional battery level LED indicators will be illuminated to provide a diagnostic aid to the operator, as described below:

Table 2

Indicator meanings

 

 

LED status

Diagnosis/Audible alarm

All LEDs

 

On bypass due to output overload; beep every half-second

 

 

 

A LED

 

On bypass due to overtemperature condition; beep every 4 sec.

 

 

 

B LED

 

On bypass due to DC bus overvoltage; beep every 4 sec.

 

 

 

C LED

 

DC-DC failure during battery mode; beep every 4 sec.

 

 

 

D LED

 

On bypass due to PFC failure; beep every 4 sec.

 

 

 

E LED

 

On bypass due to inverter failure; beep every 4 sec.

 

 

 

A&C LEDs

 

UPS failed battery test; long beep every minute

 

 

 

C&E LEDs

 

UPS shutdown due to command from communication port (SNMP); no beep

 

 

 

Battery LED Flashing

Internal Battery source not available (continuous horn). Check Battery connection,

completely power down and reboot UPS.

 

 

A&E LEDs

 

Fan locked

 

 

 

B&C

 

REPO active. UPS cannot run with REPO loop open.

 

 

 

B&D

 

UPS is OFF due to previous REPO shutdown. Autorestart disabled.

 

 

 

D&E

 

Charger Malfunction

 

 

 

Under fault conditions, the Fault indicators will be illuminated indefinitely while battery charger is operational, or for a maximum of 5 minutes while the battery charger is not operational.

If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World- wide Support Group. Please have the UPS model number and serial number available at the time of your inquiry.