![Unit IV SYSTEM OPERATION](/images/new-backgrounds/55853/5585357x1.webp)
Figure 11c - Relay Position | Figure 11d - Relay Settings |
Unit IV SYSTEM OPERATION
STARTUP PROCEDURE
CAUTION
Placing the controller in the Bypass mode inhibits its outputs, preventing actuation of any extinguishing or alarm circuits that are connected. For maximum safety, however, secure output loads (remove power from any devices that would normally be actuated by the system) before manually testing the system. Remember to place this same equipment back into service when the test is complete.
1.After setting the DIP switches and making all electrical connections, apply power to the controller.
2.Perform the Checkout Procedure.
3.If the controller appears to be operating normally (performs
NOTE
Be sure that the detector is correctly aimed at the potential hazard and that no obstructions interfere with its line of vision. UV absorbing gases should not exist between the detector and the potential hazard.
CHECKOUT PROCEDURE
CAUTION
W hen testing the system, be sure to secure all output devices to prevent unwanted activation of this equipment and remember to place these same devices back into service when the
MANUAL vi CHECK/COUNT TEST
The Autom atic vi (visual integrity) feature checks the detectors for correct response.
- 23 -