<Relay Contacts:
Norm ally open/norm ally closed contacts rated for 5 Am peres at 30 Volts DC/ 250 Volts AC
<Current Outputs:
<Dimensions: Refer to Figure 1
<Shipping Weight (approximate):
2 lbs (0.9 kilogram s)
<Certification:
CSA, NRTL/C, NEMA 4X certified for hazardous locations Class 1, Division 1, Groups B, C and D
IEC approval (Class 1, Zone 1 Groups IIB+H2 T5)
<System Sensitivity:
Sensitivity for the standard controller is field adjustable over a range of 8 through 120 counts per second (cps) in increm ents of 8 cps. The maxim um response distance is achieved at an 8 cps sensitivity setting. For applications involving high background radiation potential, the system can be
<Response Time:
Response to a saturating (high intensity) UV source is typically 10 m illiseconds for the instant alarm outputs and 0.5 seconds for the area alarm outputs when sensitivity is set for 8 cps and tim e delay is set for 0.5 seconds (m inim um settings).
Figure 1 - Controller Dimensions
DETECTOR SPECIFICATIONS
<Operating Voltage:
290Vdc ± 3Vdc (provided for controller)
- 2 -