Emerson MAN -0016-00, UVC120 manual Main Menu

Models: 0016-00 UVC120 MAN -0016-00

1 45
Download 45 pages 15.97 Kb
Page 33
Image 33

LEFT

RIGHT

 

 

DISPLAY

DISPLAY

ERROR

W HAT TO DO

290

gnd

Grounding problem with detector

Check wiring to detector, 290Vdc

290 Vdc supply.

may be shorted to ground.

 

 

290

OLo

+290 Vdc detector power too low.

Contact Factory.

290

OHi

+290 Vdc detector power too high.

Contact Factory.

12

OUT

Internal 12 Vdc supply out of

Recycle power and call factory if

operating range.1

problem persists.

5

OUT

Internal 5 Vdc supply out of

Recycle power and call factory if

operating range.1

problem persists.

24H

OUT

Controller supply is greater than

Check your power supply.

32Vdc.

 

 

 

 

24L

OUT

Controller 24 Vdc supply is less

Check your power supply.

than 18Vdc.

 

 

 

 

ch

OiH

Visual integrity error (Signal

Contact Factory.

received is too high).

 

 

 

 

chx2

OiL

Visual integrity error (Signal

Clean detector window and

 

 

received is too low).

reflector.

 

 

Reset Reed Switch is damaged, or

Make sure no magnetic objects are

rSt

E71

has been activated for more than 15

in close proximity to the switch.

 

 

seconds.

 

Ert

Err

External reset switch short error.

Make sure external reset switch is

 

not damaged or shorted to ground.

 

 

 

CFg

Err

Configuration error; incorrect dip

Check dip switch settings and

switch settings.

recycle power.

 

 

E91

Err

System RAM error.

Contact Factory.

E92

Err

Power is not stable.

Contact Factory.

E94

Err

EEPROM data not correct.

Contact Factory.

E97

Err

EEPROM reading, or writing not

Contact Factory.

correct.

 

 

 

 

Table 3 - Error Codes

1

2

If an internal power supply problem occurs, recycle power to the controller. If the problem persists, contact supplier.

If more than one channel has a vi error, the upper display will sequentially show each channel number.

If a fault has occurred, but no longer exists, the fault LED will remain illuminated and the displays will alternate between ‘nor’ and ‘Err Fnd’. To find out what the fault was, enter the error check mode by keeping the MENU/SET switch activated until ‘Chc Err’ is displayed, then activating the SELECT/RESET switch. The display should now show ‘dSP Err’. Activate the SELECT/RESET switch and the fault error codes are sequentially displayed. Once all faults have been displayed, ‘Clr Err’ is displayed. To clear the fault codes, activate the SELECT/RESET switch.

MAIN MENU

The main menu is entered by activating the MENU/SET switch for approximately 5 seconds until ‘Chc’ ‘Err’ or ‘bPS’ is shown on the displays. Repeatedly activating the MENU/SET switch will toggle through the selections. W hen the desired selection is shown on the displays, activate the

- 27 -

Page 33
Image 33
Emerson MAN -0016-00, UVC120 manual Main Menu

0016-00, UVC120, MAN -0016-00 specifications

The Emerson MAN-0016-00, UVC120, 0016-00 is a state-of-the-art device designed to meet the demands of modern industrial and commercial applications. This advanced model showcases Emerson’s commitment to innovation, providing users with reliable performance and cutting-edge technology.

One of the key features of the Emerson MAN-0016-00 is its superior control capabilities. Equipped with sophisticated algorithms, this device ensures precise and adaptable control over various processes, improving efficiency and productivity in operations. Users benefit from enhanced responsiveness to changing conditions, allowing for quick adjustments that lead to optimized performance.

Another noteworthy technology integrated into the UVC120 is its advanced user interface. The device boasts a highly intuitive control panel that facilitates easy navigation and management of settings. This user-friendly design minimizes the learning curve for operators, ensuring that they can quickly familiarize themselves with its functions. The display provides clear, real-time feedback, enabling users to monitor system performance effortlessly.

The Emerson MAN-0016-00 is also characterized by its robust construction. Designed to endure harsh environmental conditions, this model is built with durable materials that enhance its longevity and reliability. It is resistant to various industrial contaminants, ensuring consistent operation even in challenging settings.

Energy efficiency is a hallmark of the UVC120 model. By employing innovative power management technologies, it significantly reduces energy consumption without compromising performance. This emphasis on sustainability not only lowers operational costs for users but also aligns with global efforts to minimize environmental impact.

Moreover, the Emerson MAN-0016-00 incorporates advanced safety features that prioritize user protection. These include integrated alarms and emergency shut-off mechanisms that respond to detected anomalies, enhancing overall workplace safety. The design also adheres to international safety standards, ensuring compliance and peace of mind for users.

In conclusion, the Emerson MAN-0016-00, UVC120, 0016-00 stands out as an exemplary model in the field of industrial technology. Its combination of precision control, user-friendly interface, robust construction, energy efficiency, and safety features make it an ideal choice for various applications. As industries continue to evolve, devices like this play a crucial role in enhancing performance, safety, and sustainability across the board.